Description
Main Specifications
1. AC Analogue Output
1.1 AC voltage output
Range 200mV, 1V, 2V, 5V, 10V (20mV is the interpolation gear)
Adjustment range (0— 120V)%RG, RG is the range, the below is same.
Adjustment fineness 0.002%RG; Accuracy: 0.05%RG;
Stability 0.01% / 2min;
Distortion ≤ 0.02%( non-capacitive load );
1.2 Virtual AC Current Output, Protect Current (IP) Output
Range 200mV, 1V, 2V, 5V, 10V (20mV is the interpolation gear)
Adjustment range (0— 120V)%RG, RG is the range, the below is same.
Adjustment fineness 0.002%RG; Accuracy: 0.05%RG;
Stability 0.01% / 2min;
Distortion ≤ 0.02%( non-capacitive load );
1.3 Power Output
Accuracy: 0.05%RG; Stability: 0.01% / 2min
1.4 Phase Output
Adjustment range: 0° ~ 359.99° or -179.99° ~ +180°
Resolution: 0.01° ; Accuracy: 0.05°
1.5 Power Factor
Adjustment range: -1~0~+1; Resolution: 0.0001; Accuracy: 0.05%
1.6 Frequency
Adjustment range: 45Hz~65Hz; Resolution: 0.001Hz;
Accuracy: 0.002Hz;
1.7 Symmetry of three-phase voltage, current and phase
Symmetry of voltage and current < 0.02%;
Symmetry of phase < 0.05°
1.8 Voltage and current harmonic setting
Harmonic order: 2~63 times; harmonic content: 0~40%;
harmonic phase: 0° ~359.99° adjustable;
II. Remote Communication
Interface
RS-232, RS-485
III. Communication Protocol DL451-91, 9702, DISA, 101, 103, 104, DNP3, Modbus, etc.
IV. Working Condition Working temperature: 0º C~40º C, relative humidity ≤ 85%,
storage condition: - 30º C~ 60º C
V. Working Power AC 220V ± 15%
VI. Volume 450× 440 × 132 mm
VII. Weight 8kg